dpengineers

Category: New Items

  • Hydraulic Filter for Aquarius Pump

    Hydraulic Filter for Aquarius Pump

    Product Details:

    Diameter 0-1 inch, 1-2 inch, 2-3 inch, 3-4 inch, >4 inch
    Filter Medium Material Metal, Fiberglass, Microfiber, Paper
    Length 0-5 inch, 5-10 inch, 10-15 inch, 15-20 inch, 20-25 inch, >25 inch
    Usage Air Filter, Oil Filter, Steam Filter

    Hydraulic Filter for Aquarius Pump

    We are among the distinguished names in the industry for supplying and trading Hydraulic Pump Filter. The offered filter is made in tune with the international standards and ensures smooth running of the hydraulic systems. It is made from high quality of materials and is tensile in strength. This filter is used for filtering of wastes from water source.
    Features:
    Ideal for hydraulic systems

    Filters wastes
    Reliable

    Specifications:

    OD-60 mm, H-335 mm

  • Sensocon USA SERIES 211-D001I-1 Differential Pressure Transmitters

    Sensocon USA SERIES 211-D001I-1 Differential Pressure Transmitters

    Sensocon USA SERIES 211-D001I-1 Differential Pressure Transmitter

    Model – 211-D001I-1

    Pressure Range – 0-1″

    Accuracy – 1%

    • Compact Design

    • 0.25% Accuracy

    • LED Power Indication

    • 4 – 20 mA or 0 – 10 V output

    The Series 211 Differential Pressure Transmitter can accurately measure positive, negative, or differential pressure and send the corresponding 4 – 20 mA output signal. The Series 211 Differential Pressure Transmitter is not position sensitive and can be mounted in any orientation without compromising accuracy. It also features a power LED, so you always know when the transmitter is operating. The compact, lightweight design makes installation simple and easy.

    SPECIFICATIONS

    Maximum Pressure:

    Ranges ≤ 5 PSI (35 kPa) = 15 PSI (100 kPa) Max Ranges > 5 PSI (35 kPa) = 30 PSI (200 kPa) Max

    Media Compatibility:

    Air and compatible noncombustible, non-corrosive gasses

    Accuracy:

    Ranges ≤ 4″ w.c. (1 kPa) 1.0% Ranges ≥ 5″ w.c. (1.25 kPa) 0.25%

    Temperature Ranges:

    Compensated: 15° to 120°F (-10° to 50°C) Operating: -10° to 155°F (-25° to 70°C)

    Thermal Effect:+/- 0.028% FS/°F (+/- 0.050%/°C)

    Stability: +/- 0.25% FS/year

    Output Signal: 4-20 mA, 2 wire or 0-10V

    Loop Resistance: 250 Ω @ 24 VDC

    Power Supply: 12-30 VDC

    Housing Material: ABS Plastic

    Electrical Connections: screw terminals

    Process Connection: Push on connection for 3/16″ I.D. tubing

    Agency Approvals: CE